Fuses

02:06 / Posted by tech data / comments (0)

The most basic overcurrent protective element on the system is a fuse. Fuses are relatively inexpensive and maintenance-free. For those reasons, they are generally used in large numbers on most utility distribution systems to protect individual transformers and feeder branches
(sometimes called laterals or lateral branches).

Figure shows a typical overhead line fused cutout. The fundamental purpose of fuses is to operate on permanent faults and isolate (sectionalize) the faulted section from the sound portion of the feeder. They are positioned so that the smallest practical section of the feeder is disturbed. Fuses detect overcurrent by melting the fuse element, which generally is made of a metal such as tin or silver. This initiates some sort of arcing action that will lead to the interruption of the current. There are two basic kinds of fuse technologies used in power systems:

1. Expulsion fuses
2. Current-limiting fuses

The essential difference between the two is the way the arc is quenched. This also gives the fuses different power quality characteristics. An explusion fuse creates an arc inside a tube with an ablative coating. This creates high-pressure gases that expel the arc plasma and fuse remnants out the bottom of the cutout, often with a loud report similar to a firearm. This cools the arc such that it will not reignite after the alternating current naturally goes through zero. This can be
as short as one-half cycle for high currents to several cycles for low fault currents. This determines the duration of the voltage sag observed at loads. An expulsion fuse is considerably less expensive than a currentlimiting fuse.

A current-limiting fuse dissipates the energy in the arc in a closed environment, typically by melting a special sand within an insulating tube. This process actually quenches the arc very quickly, forcing the
current to zero before that would naturally occur. This can have somebeneficial impacts on the voltage sag characteristics.

Labels:

ELECTRICAL EARTHING

09:27 / Posted by tech data / comments (3)

WHAT IS EARTHING ?
“Earthing” may be described as a system of electrical connections to the general mass of earth. The characteristic primarily determining the effectiveness of an earth electrode is the resistance, which it provides between the earthing system and the general mass of earth.

PURPOSE OF EARTHING ?
The earthing of an electrical installation has two purposes:
• To provide protection for persons or animals against the danger
• To maintain the proper function of the electrical system.

QUALITIES OF A GOOD EARTHING SYSTEM:
• Must be of low electrical resistance
• Must be of good corrosion resistance
• Must be able to dissipate high fault current repeatedly

WHERE IS EARTHING REQUIRED :
• Telecommunication
• Transmission
• Substations & Power Generations
• Transformer Neutral earthing
• Lightning Arrestor Earthing
• Equipment Body Earthing
• Data Processing Centers
• Refineries & manufacturing Facilities
• Food Processing
• Water Treatment Plants
• Remote & Central Office Digital Switches
• Heavy Industries
• College, Hospitals, Banks
• Residential Building THE CHIEF REQUIREMENT OF GOOD EARTHING IS LOW SOIL RESISTIVITY.
Soil Resistivity (specific resistance of the soil) is usually measured in Ohm metres, one Ohm metre being the resistivity the soil has when it has a resistance of one Ohm between the opposite faces of a cube of soil having one metre sides. The other unit commonly used is the Ohm centimetre; to convert Ohm metres to Ohm centimetres, multiply by 100. Soil resistivity varies greatly from one location to another. For example, soil around the banks of ariver have a resistivity in the order o f1.5 Ohm metres. In the other extreme, dry sand in elevated areas
can have values as high as 10,000 Ohm metres.

PRINCIPAL FACTORS AFFECTING SOIL RESISTIVITY
The factors chiefly affecting soil resistivity are:

1. Type of Soil
The soil composition can be: clay, gravel, loam, rock, sand, shale, silt, stones, etc. In many
locations, soil can be quite homogenous, while other locations may be mixtures of these soil types in varying proportions. Very often, the soil composition is in layers or strata, and it is the resistance of the varying strata, especially at sub-soil level and lower where the moisture content is not subject to drying out, that is important in securing a good electrical earth. Refer Table 1 for typical soil resistivity values.


2. Climate
Obviously, arid and good rainfall climates are at opposite extremes for conditions of soil
resistivity.


3. Seasonal Conditions
The effects of heat, moisture, drought and frost can introduce wide variations in “normal” soil
resistivity. Soil resistivity usually decreases with depth, and an increase of only a few percent of moisture content in a normally dry soil will markedly decrease soil resistivity. Conversely, soil temperatures below freezing greatly increase soil resistivity, requiring earth rods to be driven to even greater depths. See Table 2 for variations of soil resistivity with moisture content, and Table 3 for variations of soil resistivity with temperature.

4. Other Factors
Other soil properties conducive to low resistivity are chemical composition, soil ionisation, homogeneous grain size and even grain distribution - all of which have much to do with retention of soil moisture, as well as providing good conditions for a closely packed soil in good contact with the earth rod. In view of all the above factors, there is a large variation of soil resistivity between different soil types and moisture contents.

Every earth is an individual and the only way to know that an earthing installation meets code
requirements is to carry out proper resistance measurements on site. There are a variety of test instruments available , however, they can be generally categorised as threeterminal of four-terminal test instruments.

TYPES OF EARTH RODS
At one time or another, all manners of conductor materials and shapes have been installed in the ground to provide an electrical earth. These materials range from cast iron plates, tubes, galvanised steel stakes, copper strip, metallic rod, wire and water pipe. Taking into account conductivity, high resistance to atmospheric corrosion and soil attack, ease and economy of installation and overall reliability, the steel rod clad with either copper or stainless steel has proven its superiority over all others. The clad steel rod is simple to install, its connection to the earthing system is easily made, and the installation is readily accessible for inspection and test. Additionally, by the use of deep driving techniques, extendible earth rods gave been developed to reach underlying strata of low permanent resistivity unaffected by seasonal drying.

STEEL CORE EARTH RODS HAVE THE BEST ATTRIBUTES
Electrically, a good earth rod should have a low intrinsic resistance and be of sufficient section to carry high currents without damage when called upon. Mechanically, its physical properties should exhibit strength, have a rigid core for easy driving and be of durable, corrosion resistant material.

EARTH ROD LENGTH MORE IMPORTANT THAN ROD DIAMETER
Apart from considerations of mechanical strength, there is little advantage to be gained from increasing the earth rod diameter with the object in mind of increasing surface area in contact with the soil. The usual practice is to select a diameter of earth rod, which will have enough strength to enable it to be driven into the particular soil conditions without bending or splitting. Large diameter rods may be more difficult to drive than smaller diameter rods. The depth to which an earth rod is driven has much more influence on its electrical resistance characteristics than has its diameter. This is because it is not the actual area of contact with the soil that counts, so much as the total resistance area of the sheath or shell surrounding the earth rod.

Labels:

Load Break Switches (LBS)

10:22 / Posted by tech data / comments (0)

Load Break Switches and Isolators for voltages ranging from 3.3kv to 36 kv offers a high technical standard and economy over the years for the switchgear manufacture with dependability, reliabilty and versatility.

The salient feature of Load Break Switch is its ability to permit load connections even under a short circuit condition without danger to the operating personnel. A high speed(snap action) make and break ensures a fast switching action and the very special design of arc chutes having excellent extinguishing properties for both high and low currents, suitability of mounting in horizontal or vertical plane etc. prove the versatility of these switches.

Main Features:
• High Operating reliability
• Simple maintenance and inspection
• High dynamic & thermal strength
• Special tubular arc-chutes
• Current interruption without visible arcs.
• Simple driving mechanism

Due to the compact design of individual cubicles, and the feasibility of mounting the switches in different directions, economy in space is achieved , with ample scope for future extension. The triple pole load break switch can be used for switching of transformer feeders, overhead lines, capacitor banks, cable feeders, and ring mains. For protection against circuits H.T.Fuses can be offered with the switch.

Labels:

Types of circuit breaker

11:17 / Posted by tech data / comments (1)

MCB (Miniature Circuit Breaker)—rated current not more than 100 A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category. MCCB (Moulded Case Circuit Breaker)—rated current up to 1000 A. Thermal or thermal-magnetic operation. Trip current may be adjustable.Air circuit breaker—Rated current up to 10,000 A. Trip characteristics often fully adjustable including configurable trip thresholds and delays. Usually electronically controlled, though some models are microprocessor controlled. Often used for main power distribution in large industrial plant, where the breakers are arranged in draw-out enclosures for ease of maintenance.

Vacuum circuit breaker—With rated current up to 3000 A, these breakers interrupt the current by creating and extinguishing the arc in a vacuum container. These can only be practically applied for voltages up to about 35,000 V, which corresponds roughly to the medium-voltage range of power systems. Vacuum circuit breakers tend to have longer life expectancies between overhaul than do air circuit breakers. Sulfur hexafluoride -High-voltage circuit-breakers have greatly changed since they were first introduced about 40 years ago, and several interrupting principles have been developed that have contributed successively to a large reduction of the operating energy. These breakers are available for indoor or outdoor applications, the latter being in the form of breaker poles housed in ceramic insulators mounted on a structure.
Current interruption in a high-voltage circuit-breaker is obtained by separating two contacts in a medium, such as SF6, having excellent dielectric and arc quenching properties. After contact separation, current is carried through an arc and is interrupted when this arc is cooled by a gas blast of sufficient intensity.


Future perspectives:In the near future, present interrupting technologies can be applied to circuit-breakers with the higher rated breaking currents (63 kA to 80 kA) required in some networks with increasing power generation.
Self blast or thermal blast circuit breakers are nowadays accepted world wide and they are in service for high voltage applications since about 15 years, starting with the voltage level of 72.5 kV. Today this technique is also available for the voltage levels 420/550/800 kV.

Labels:

Circuit breaker

10:05 / Posted by tech data / comments (0)

A circuit breaker is an automatically-operated electrical switch which is designed to protect an electrical circuit from damage caused by overload or short circuit. Unlike a fuse which operates once and then has to be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.

Circuit breakers are made in varying sizes, from small devices which protect an individual household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city.